Testing a FINCH Display with Your Titan Probe

Testing a FINCH Display with Your Titan Probe

ⓘ

Before You Begin

Review Clearance Requirements for Probe and Transmitter Installations to confirm proper spacing and setup.

Overview

Background

When your tank is empty, you can test the probe and FINCH display to confirm that the system is programmed correctly and responds at different points along the tank.

The FINCH display will typically show 2Lo when there is little or no liquid in the tank. By manually simulating contact with liquid, you can confirm that the display responds with the level or volume programmed for the point being tested.

FINCH display and Titan probe testing example

Testing procedure

Testing the Probe with the FINCH Display

The testing method depends on the type of probe installed.

Coaxial Probe

A coaxial probe has an inner rod inside a thicker outer tube. The holes along the outer tube allow you to reach the inner rod and simulate a product level.

  1. 1

    Choose a Hole

    Choose a hole at the level you want to test.

  2. 2

    Insert the Tool

    Insert a conductive metal tool, such as a metal rod or screwdriver, through the hole until it touches the inner rod.

    Holes along a Titan coaxial probe
  3. 3

    Observe the Display

    Observe the FINCH display. It should show the level or volume programmed for that point.

    Using a metal tool to touch the inner rod of a coaxial probe
  4. 4

    Repeat at Additional Holes

    Repeat at additional holes to confirm the display responds at different heights.

Example: If you insert the tool through the third hole from the bottom and touch the inner rod, the display should show the value programmed for that height.

Dual Rod Probe

Touch both rods at the same time, then move your fingers up and down the probe to simulate different product levels. The FINCH display should change as the contact point moves along the probe.

ClearView Probe

The ClearView probe is a type of coaxial probe with zero deadband. Its outer tube has slits rather than holes.

Insert a conductive metal tool through a slit until it touches the inner rod. Move to additional slits to simulate different product levels and confirm that the FINCH display responds with the expected level or volume.

System response: If the system is connected to rack controls, simulating product contact should also produce the expected non-permissive response. Follow your site procedures when confirming this function.

Best practices

Testing Tip

Test multiple points along the probe to confirm that the FINCH display responds consistently at different heights. If the reading does not match the programmed level, confirm that you are making proper contact with the required probe surface and repeat the test at another point.