The Spill Alarm Specifications for TD80
The TD80 Transmitter supports two Spill alarm reset methods. Which methods are available depends on the probe type installed.
DR
TD80 Dual Rod Transmitter
Band-clear only
CX
TD80 Coaxial Transmitter
Band-clear or auto-clear
Band-Clear Spill Alarm Reset
TD80: the liquid level must be detected at least 2” below the HH alarm level and within 16.5” of the Spill alarm level.
Auto-Clear Spill Alarm Reset
TD80: liquid must be detected at least 2” below the HH alarm level.