The Spill Alarm Specifications for TD80

The Spill Alarm Specifications for TD80

The TD80 Transmitter supports two Spill alarm reset methods. Which methods are available depends on the probe type installed.

DR

TD80 Dual Rod Transmitter

Band-clear only

CX

TD80 Coaxial Transmitter

Band-clear or auto-clear

Band-Clear Spill Alarm Reset

TD80: the liquid level must be detected at least 2” below the HH alarm level and within 16.5” of the Spill alarm level.

Auto-Clear Spill Alarm Reset

TD80: liquid must be detected at least 2” below the HH alarm level.