Error Codes Summary
The FINCH Display is designed to not only indicate a malfunction but also provide helpful information about it. This includes error codes and other indications that can assist in the troubleshooting process. It is important to take note of the specific error code that appears on the FINCH display and any other indications to discuss when addressing the breakdown.
Below is a list of all of the potential error codes, listed in numerical order, that you might see on your FINCH display and how to address them.
| Error Code | Description | Solution |
|---|---|---|
| Dashed lines (-----) | Communication error between Transmitter and FINCH display | Review the wiring to ensure that the wires are in the correct order. |
| E0000 | Could not measure level |
Note: If this doesn't resolve the issue, you will need to replace your transmitter. |
| E0001 | Too many samples rejected (too much turbulence) |
Move Probe to Less Turbulent Area
Note: If this doesn't resolve the issue, you will need to replace your transmitter. |
| E0002 | Internal transmitter error |
Update the Transmitter's Firmware. Note: If this doesn't resolve the issue, you will need to replace your transmitter. |
| E0010 | Internal measurement transmitter error |
Update the Transmitter's Firmware. If this doesn't resolve the issue, there may be water inside your transmitter that causes it to fail. If this is the case, you will need to replace or repair the transmitter. |
| E0020 | Probe and/or Transmitter Connection Issues |
|
| E0080 | Strapping Table Issue: HH alarm is too close to Spill level |
|
| E0081 or NOSTB | Strapping Table Issue: No strapping table programmed in the Transmitter |
Program a strapping table using SensorLink or Titan Install. More Info |
| E0082 | Strapping Table Issue: Invalid strapping table on startup |
Reprogram the transmitter with the latest version of SensorLink or Titan Install. More Info |
| E0083 | Strapping Table Issue: Invalid strapping table during operation |
TD80 transmitter ONLY
Note: If this doesn't resolve the issue, you will need to replace your transmitter with a TD100. |
| E0084 | Strapping Table Issue: Invalid strapping table during runtime | Reprogram the transmitter with the latest version of SensorLink or Titan Install. |
| E0090 | Outdated transmitter firmware version and missing fluid calibration |
If this is a brand new unit, this error code appears because the tank has not been filled yet.
|
| E0091 | Outdated transmitter firmware version and missing fluid calibration |
|
| E0092 | Probe and/or Transmitter Connection Issues |
Check if the shorting block is correctly installed on the probe. Check if your probe is longer than the strapping table. Note: This error will appear if you are connecting the transmitter right to the FINCH (without the probe) for testing purposes. |
| E0093 | Outdated transmitter firmware version and measurement error |
Update the TD100 firmware to the latest version. Check probe and transmitter for damage. |
| E0094 | Outdated transmitter firmware version and measurement error |
|
| E0095 | Memory Failure on transmitter | – |
| E0096 | Memory Failure on transmitter | – |
| E0097 | Memory Failure on transmitter | – |
| E0098 | Memory Failure on transmitter | – |
| E01A0 | Wireless Module Communication Error |
FINCH II-W/6W Display ONLY |
| E0400 | SV1/SV2 Communication Error | Contact Titan Service & Support. |
| E0401 | RS232 Communication Error | Contact Titan Service & Support. FINCH II Display ONLY. |
| E0402 | SV3/SV4 Expansion Card Communication Error | Contact Titan Service & Support. FINCH II-6W Display ONLY. |
| E0403 | SV5/SV6 Expansion Card Communication Error | Contact Titan Service & Support. FINCH II-6W Display ONLY. |
| E0404 | Wireless communication module failure (Bluetooth module) | Contact Titan Service & Support. FINCH II-W/6W Display ONLY. |
| E0500 | Global Acknowledge Failure – Secondary FINCH display not detected |
For FINCH II Displays: Check B-DIP, switch 3 is ON. Unlock the hardware setting by turning B-DIP, switch 4 OFF. If this doesn't resolve the issue, you will need to replace/repair your FINCH II. For FINCH III Displays: Use Titan Install to configure your secondary FINCH III display. |
| E0700 | Unable to read compartment or DIM/SLEEP settings | Possibly a defective FINCH II display. |
| E0701 | FINCH II Relay Alarm map has not been configured | Possibly a defective FINCH II display. |
| E0702 | FINCH II can't read sector 1 settings from Flash |
Note: If this doesn't resolve the issue, you will need to replace or repair your FINCH II display. |
| E0703 | FINCH II serial flash timeout |
Note: If this doesn't resolve the issue, you will need to replace or repair your FINCH II display. |
| E0705 | Old/Incorrect Configuration Settings | |
| E0780 | Engine control relay issue | Your FINCH II board needs to be repaired or replaced. |
| E0781 | Pump control relay issue | Your FINCH II OR FINCH III board needs to be repaired or replaced. |
| E0782 | Light control relay issue | Your FINCH II OR FINCH III board needs to be repaired or replaced. |
| E0783 | Horn control relay issue | Your FINCH II OR FINCH III board needs to be repaired or replaced. |
| E0784 | Issue with Rack Control configurations on FINCH III | FINCH III only error. |
| E0800 | No communication on specific compartment |
Inspect and fix the wiring connection between the transmitter and the FINCH. Note: If this doesn't resolve the issue, you will need to replace or repair your transmitter. |
| E0801 | System Initialization Failure |
Cycle the power to the FINCH II or FINCH III. Note: If this doesn't resolve the issue, you will need to replace or repair your FINCH display. |
| E0802 | Input Voltage to FINCH display is too low |
Use a digital multimeter to check the voltage. Ensure it is greater than 8V. Look for corroded wire connections where the power cable connects. Note: The E0802 error code may be accompanied by other codes such as E0780. There may be multiple errors happening as a result of low or unstable power. More Info |
| E0803 | Input Voltage to FINCH display is too high |
Use a digital multimeter to check the voltage. Ensure it is less than 30V. Look for wire connection issues along the input power. |
| E0804 | Automatic System Reset |
Note: If this doesn't resolve the issue, you will need to replace or repair your FINCH display. |
| E0901 | No Transmitter found | – |
| E0902 | Incomplete Transmitter configuration | – |
| E0903 | Communication error | – |
| E0904 | Incompatible Transmitter connected | – |
| E0905 | Transmitter Disconnected | – |
| E0907 | Setup Error | FINCH III Only. Scan FINCH III using Titan Install to reconfigure your system. |
| E1111 | Issue supplying power to the transmitter(s) | – |
| 8888 | Input voltage issue |
Check input voltage.
|