My FINCH Display Shows a Level on an Empty Tank
The following steps walk you through the troubleshooting steps to take when your FINCH Display is showing a reading but the tank is empty.
| Step | Details | Additional Info |
|---|---|---|
| Step 1 | Ensure your tank is actually empty. | Please skip this step if you are not able to or not allowed to look inside your tank. |
| Step 2 |
Check your probe for physical damage, defects, or product build up.
|
Please skip this step if you are not able to or not allowed to look inside your tank. |
| Step 3 | Perform an offset calibration. Is this a new installation, or has it been running for a while? Is the probe not dead center? Is the tank double conical (where there is a dip at the bottom)? If it isn't, we would need to adjust the strap chart. | |
| Step 4 |
Verify how the strapping table has been programmed on your TD Transmitter. Make sure to confirm the probe length is the same height as the strap chart. |
Tip: Refer to Titan Logix's Programming Guide for more information. |
| Step 5 | Your TD transmitter may be defective. Replace your transmitter with a serviceable unit that has been programmed with the same information as the one it is replacing. |