Dual Rod Probe Installation

Dual Rod Probe Installation

Titan Logix's probes are shipped longer than required to fit all tank installations. Cut your Dual Rod Probe to length before installing it in the tank.

▶

Watch the installation videos

Click the link below to watch our step-by-step installation videos for this process.

Probe Installation Videos

Installation videos

Cutting the Dual Rod Probe

  1. 1

    Measure Tank Height

    Measure the inside of your tank from the top edge of the 1" NPT top fitting to the bottom of the cone or bracket.

  2. 2

    Measure Probe Length

    Measure the length of your probe starting from the threaded end.

  3. 3

    Add Cutting Allowance

    For Dual Rod Probes, add an additional 1.5" to the tank height to know where to cut your probe.

    Tip: Dual Rod Probe Length = Tank height + 1.5"
  4. 4

    Cut the Probe

    Cut the probe at the end of the shorting block to ensure accurate measurements and a proper fit.

Installation

Installing the Probe

  1. 1

    Insert Probe into Tank

    Once the probe is cut to fit inside the tank, carefully insert the probe through the top fitting, resting the shorting block inside the anchor cone.

  2. 2

    Verify Clearance Gap

    Ensure there is a 1/2" gap between the bottom of the tank and the bottom of the shorting block inside the anchor cone.

  3. 3

    Tighten Fitting

    Tighten the probe into the top fitting.

  4. 4

    Confirm Alignment

    Ensure that the probe is not bent or twisted after installation.

For tips on positioning your probe after installation, see: Dual Rod Probe Orientation Best Practices

Best practices

Probe Orientation After Installation

Proper positioning of the Titan Logix Dual Rod Probe after installation in the tank is vital for enhancing the performance of the Titan system in heavy oil applications.

When the dual rods are oriented parallel to the tank, the movement of the thicker product may cause them to touch. This contact can result in the rods sticking together, leading to inaccurate or stuck level readings on your FINCH display.

The probe's orientation is critical in avoiding these problems. After installation, the probe can be adjusted with a wrench to set the rods either horizontally or at a 90-degree angle to the trailer's length. This configuration enables the liquid's movement to flow through each rod separately, preventing the rods from being pushed together.

Ensure that the probe is aligned correctly following installation to optimize its mechanical performance and significantly minimize the risk of loading issues.