Clearing SPILL Alarm on a FINCH 5332E

Clearing SPILL Alarm on a FINCH 5332E

Clear a stuck SPILL alarm

If a tank is unloaded while system power is off, the FINCH 5332E may display a flashing SPILL alarm when power is restored — the monitor detects a level change it interprets as a system error. On a TD80 system with a FINCH 5332E display, use this procedure to clear the condition.

  1. 1

    Clear the HH Alarm

    Press the buttons in the following sequence: UP → UP → DOWN → UP. This will clear the HH alarm if it is active.

  2. 2

    Verify Tank Level

    Confirm that the tank is not full before proceeding.

  3. 3

    Enter Calibration Mode

    1. Power down the FINCH 5332E display.
    2. Press and hold either the UP or DOWN arrow button.
    3. While holding the button, power up the display.
    4. Continue holding the button until "CAL" appears on the display, then release the button.
  4. 4

    Allow Calibration to Complete

    1. The display will flash "CAL" for approximately 10 seconds.
    2. After the flashing stops, the display will show either a numeric level value or "SPILL".
  5. 5

    Restart the Display

    1. Power down the display again.
    2. Power the display back up normally.
Expected Result

What you should see

After completing this procedure, the display should start up showing either "2Lo" or a valid tank level reading. The SPILL alarm should now be cleared.

display copy
!
If the SPILL Alarm Remains Active

If the SPILL alarm does not clear after performing this procedure, another fault is likely present in the system and additional troubleshooting will be required.