- Titan Help Center
- Operating Your System
- FINCH Display
Resetting Alarm Relay Mapping to factory defaults through front panel
There is a button sequence that can be entered on the front panel of the FINCH II that will reset the alarm relay mapping to factory default. This is extremely useful is you suspect that a customer has tampered with the relay mappings and the relays aren’t working.
The button sequence is HORN BYPASS, UP ARROW, UP ARROW, COMP SELECT, HORN BYPASS.
The buttons must be pressed in that order and consecutive to each other for the command to be recognized.
Note:
This feature is only available in firmware versions 1.03.00 and higher. Refer to Updating my Firmware for more info on these steps.
Need more help?
Contact one of our Titan Logix's Service Team members for more technical assistance.
Phone: 1-877-462-4085 (ext. 2)
Email: service@titanlogix.com