FINCH II Fill & Fall Alarm Settings

The Fill Alarm

  • Purpose
    • Fill alarm allows the operator to set a warning at a predetermined volume while loading.
    • Used to stop loading at a predetermined volume or warn of the approaching High-High alarm at the maximum safe volume.

  • Fill Alarm Setting
    • While in Monitor or Display mode:
      • Select the compartment for the Fill alarm setting.
      • press and hold the UP button for more than 2 seconds and then release the button.
    • Fill” flashes 3 times.
    • Use the UP and DWN buttons to set the Fill alarm volume.
      • Momentary press changes the volume by 1 unit.
      • Press and hold to rapidly change the volume.
      • No button press for 5 seconds ends the Fill alarm setting.

  • Fill Alarm Acknowledge
    • The active Fill alarm displays a flashingFILL” and the current volume.
    • Clear the alarm by pressing the ACK

 

The Fall Alarm

  • Purpose
    • Fall alarm allows the operator to set a warning at a predetermined volume while unloading.
    • Used to stop unloading at a predetermined volume or warn of the approaching minimum safe volume.

  • Fall Alarm Setting
    • While in Monitor or Display mode:
      • Select the compartment for the Fall alarm setting.
      • press and hold the DWN button for more than 2 seconds and then release the button.
    • FALL” flashes 3 times.
    • Use the UP and DWN buttons to set the Fall alarm volume.
      • Momentary press changes the volume by 1 unit.
      • Press and hold to rapidly change the volume.
      • No button press for 5 seconds ends the Fall alarm setting.

  • Fall Alarm Acknowledge
    • The active Fall alarm displays a flashing “FALL” and the current volume.
    • Clear the alarm by pressing the ACK

 


Need more help?

Contact one of our Titan Logix's Service Team members for more technical assistance.

Phone: 1-877-462-4085 (ext. 2)

Email: service@titanlogix.com

Documentation Support: https://www.titanlogix.com/support/downloads/