Titan Logix's older FINCH Displays, FINCH 5332E and FINCH 5332 IN-CAB Display provide LED numeric display of volume information, alarms and system error codes from the TD80 and TD100 transmitter.
You are able to manually calibrate both of these displays, which can be connected to either a TD80 or TD100 transmitter.
FINCH 5332E | FINCH 5332 IN-CAB |
Complete the following steps to manually calibrate your FINCH 5332E and/or FINCH 5332 IN-CAB Display.
1. Hold down an arrow button (doesn't matter if it is up or down arrow) on the front of the display and then turn on the power.
2. Continue to hold the arrow button until you see the word CAL on the display.
3. Once you see CAL on the display, release the arrow button.
4. When the display shows the volume, press the up or down arrows on the display to adjust the display volume to match the measured amount of fluid.
5. Turn the power off and back on again to complete the offset calibration.
Caution
Please note that there needs to be at least 6 inches of liquid in the tank, or the display will show 2Lo because of a low tank level.
Need more help?
Contact one of our Titan Logix's Service Team members for more technical assistance.